Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Protective Gap |
Still deciding? Get samples of US$ 3.4/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameters :
Type | AC SPD | |||||
Protection level B,C,D Grade | D,C,B | |||||
Rated Operating Voltage Un(V) | 380V/220V | |||||
Max continuous operating voltage Uc/V | 275V | 320V | 385V | 385V | 385V | 420V |
Voltage protection level up(KV) | ≤1.0 | ≤1.2 | ≤1.8 | ≤2.0 | ≤2.2 | ≤2.8 |
Maximum discharge current Imax(8/20μs)KA | 5 | 10 | 20 | 30 | 40 | 60 |
Nominal discharge current In(8/20μs)KA | 10 | 20 | 40 | 60 | 80 | 100 |
Response times | ≤25 | |||||
Test Standard | IEC61643.1, GB18802.1 | |||||
Operating Environment | -40 degree to + 85 degree | |||||
Max Connection Line | 35mm2 hard wire/35mm2 strand wire copper line | |||||
Recommended Connection Line | 16mm2 hard wire/25mm2 strand wire copper line | |||||
Installation | Standard Rail 35mm | |||||
Material of outer covering | Burning -proof Nylon |
Product Display
FAQ :
Surge protector, also name lightning arrestor protector, it's provides safety protection for various electronic equipment, instruments, and communication lines. When an electrical circuit or communication line suddenly generates a peak current or voltage due to external interference, the surge protector can conduct the shunt in a very short time, thereby avoiding the damage of the surge to other equipment in the circuit.